ETIMAT P10 3p C13 15kA Miniature circuit breaker
- ETI Code:
- 001901829
- Special Environment:
- EN/IEC 60947-2
- Application:
- EN/IEC 60898-1; EN/IEC 60947-2
- Rated current:
- 13 A
- Tripping characteristic:
- C
- Number of poles:
- 3
- Short circuit capacity:
- 15 kA
- Voltage type:
- AC
- Rated impulse withstand voltage Uimp:
- 6 kV
- Rated AC voltage:
- 415 V
- Rated Frequency:
- 50/60 Hz
- Rated cross section:
- 1-25 mm²
- Standards:
- EN/IEC 60898-1; EN/IEC 60947-2
- Function:
- MCB
2 Documents
22 Logistics
Product
- Net depth
- 220 mm
- Net weight of the product
- 367 g
- Net width
- 91 mm
- Net height
- 79 mm
- Stock unit of measure
- pcs
- EAN code for a single product
- 3838400136152
Basic Packaging
- EAN code for a basic packaging
- 3838400136169
- Basic packaging weight
- 1.16 kg
- Basic Packaging Dimensions Depth
- 220 mm
- Basic Packaging Dimensions Height
- 79 mm
- Basic packaging volume
- 1.582 dm³
- Basic Packaging Dimensions Width
- 91 mm
- Basic packaging quantity
- 4 pcs
Transport Packaging
- Transport packaging weight
- 10.83 kg
- Transport packaging volume
- 17.272 dm³
- Transport packaging quantity
- 36 pcs
- Customs tariff
- 85362010
- Transport Packaging Dimensions Height
- 253 mm
- Transport Packaging Dimensions Width
- 233 mm
- Transport Packaging Dimensions Depth
- 293 mm
- EAN code for a transport packaging
- 3838400136176
- Pallet quantity
- 1,872 pcs
28 ETIM
- Additional equipment possible
- Yes
- Rated insulation voltage Ui
- 500 V
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
- 15 kA
- Built-in depth
- 70 mm
- Connectable conductor cross section solid-core(Max)
- 25 mm²
- Voltage type
- AC
- Connectable conductor cross section multi-wired(Max)
- 25 mm²
- Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
- 10 kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
- 15 kA
- Rated impulse withstand voltage Uimp
- 6 kV
- Frequency(Min)
- 50 Hz
- Degree of protection (IP)
- IP20
- Ambient temperature during operating(Min)
- -60 °C
- Release characteristic
- C
- Over voltage category
- 3
- Number of poles (total)
- 3
- Connectable conductor cross section solid-core(Min)
- 1 mm²
- Pollution degree
- 2
- Frequency(Max)
- 60
- Connectable conductor cross section multi-wired(Min)
- 1 mm²
- Number of protected poles
- 3
- Rated voltage
- 415 V
- Current limiting class
- 3
- Rated current
- 13 A
- Ambient temperature during operating(Max)
- 70 °C
- Flush-mounted installation
- Yes
- Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
- 10 kA
- Width in number of modular spacings
- 3
25 Tags
Related News & Updates
Nazivna kratkostična zmogljivost
Nazivna kratkostična zmogljivost predstavlja največjo vrednost kratkostičnega toka, ki ga lahko odklopnik ali varovalka prekine. Vsaka zaščitna naprava je zasnovana za določeno nazivno moč in s tem tudi za določen nazivni (obremenitveni) tok. Kratkostični tokovi lahko trajno poškodujejo zaščitne naprave zaradi prekomernega segrevanja in sproščene energije. V elektroenergetiki uporabljamo različne vrste električne opreme (zaščitnih naprav) z različnimi tehničnimi lastnostmi, ki vključujejo tudi kratkostično zmogljivost. Poglejmo nekaj primerov.
Rated short-circuit breaking capacity
Rated short-circuit breaking capacity represents the highest value of short-circuit current that a circuit breaker or fuse is capable of interrupting. Each protective device is designed for a specific rated power and therefore for a specific rated (load) current. Short-circuit currents can permanently damage protective devices due to excessive heat and the energy released. In electrical power engineering, we use various types of electrical equipment (protective devices) with different technical specifications that also describe short-circuit capacity. Let us look at some examples.