NBS-E 630/4L LCD 630A 4P Molded Case Circuit Breaker
- ETI Code:
- 004673146
- Application:
- 60947
- Rated current:
- 630 A
- Number of poles:
- 4
- Connection type:
- front connection
- Rated impulse withstand voltage Uimp:
- 8 kV
- Rated short-circuit breaking capacity at 415V Icu/Ics:
- 36 kA
- Rated operational voltage (AC):
- 690 V
- Rated Insulation Voltage:
- 1,000 V
- Thermal Adjustment:
- (0,4-1) x In
- Magnetic adjustment:
- (1,5-12) x Ir
- Adjustable or fixed:
- adjustable
- Standards:
- 60947
- Function:
- MCCB
18 Logistics
Product
- Net weight of the product
- 8.5 kg
- Stock unit of measure
- pcs
Basic Packaging
- EAN code for a basic packaging
- 3838895941842
- Basic packaging weight
- 7.13 kg
- Basic Packaging Dimensions Depth
- 284 mm
- Basic Packaging Dimensions Height
- 185 mm
- Basic packaging volume
- 10.245 dm³
- Basic Packaging Dimensions Width
- 195 mm
- Basic packaging quantity
- 1 pcs
Transport Packaging
- Transport packaging weight
- 21.99 kg
- Transport packaging volume
- 35.931 dm³
- Transport packaging quantity
- 3 pcs
- Customs tariff
- 85362090
- Transport Packaging Dimensions Height
- 210 mm
- Transport Packaging Dimensions Width
- 295 mm
- Transport Packaging Dimensions Depth
- 580 mm
- EAN code for a transport packaging
- 3838895941859
- Pallet quantity
- 81 pcs
18 ETIM
- Rated voltage(Max)
- 690 V
- Motor drive optional
- Yes
- Overload release current setting(Min)
- 252 A
- Complete device with protection unit
- Yes
- Adjustment range short-term delayed short-circuit release(Min)
- 378 A
- Rated permanent current Iu
- 630 A
- Degree of protection (IP)
- IP20
- Type of control element
- Toggle
- Position of connection for main current circuit
- Front side
- Integrated earth fault protection
- Yes
- Type of electrical connection of main circuit
- Screw connection
- Adjustment range short-term delayed short-circuit release(Max)
- 7,560 A
- Number of poles
- 4
- Overload release current setting(Max)
- 630 A
- Rated voltage(Min)
- 415 V
- Device construction
- Complete device in housing
- Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
- 36 kA
- With switched-off indicator
- Yes
0 Software & drivers
25 Tags
Video
Related News & Updates
Nadgradnja ETIBREAK NBS: Dodajanje funkcije daljinskega sprožnika (Shunt Trip)
Dodajanje daljinskega sprožnika (shunt trip) na kompaktne odklopnike ETIBREAK NBS omogoča daljinski izklop — ključno za večjo varnost in avtomatizacijo. V tem vodiču je predstavljen celoten postopek namestitve, od priprave do testiranja. Ne glede na to, ali nadgrajujete obstoječo omaro ali nameščate nov sistem, pravilna namestitev zagotavlja zanesljivo delovanje in brezhibno vključitev v vaš krmilni sistem. Poglejmo si korake.
ETIBREAK NBS Upgrade: Adding a Shunt Trip Function
Adding a shunt trip to your ETIBREAK NBS moulded case circuit breakers (MCCBs) provides remote shutdown capability — crucial for improving safety and automation. This guide outlines the full installation process, from prep to testing. Whether you're upgrading an existing panel or setting up a new system, proper installation ensures reliable performance and seamless integration with your control setup. Let’s walk through each step to get it done right.