Tehnical support
This email address is being protected from spambots. You need JavaScript enabled to view it.

RCCB EFI-P4 A 63/0.5 002061543

Specifications

ETI Code:
002061543
Description:
EFI-P4 A 63/0.5
Class name:
RCCB
Rated current (A):
63
Rated residual operating current IΔn (A):
0.5
Type:
A
No. Of poles:
3+N
Rated conditional short-circuit current Inc (kA):
10
Tripping time:
Instantaneous
Rated voltage (V):
415
Rated Frequency (Hz):
50/60
Terminals (mm2):
1-25
Standards:
IEC/EN 61008

Documents

Product

EAN code for a single product
3838895866527
Net weight of the product
290 g
Customs tariff
85362010

Basic packaging

Basic packaging quantity
1
EAN code for a basic packaging
3838895866527
Basic packaging weight
0.32 kg
Basic packaging volume
0.5

Transport packaging

Transport packaging quantity
27
EAN code for a transport packaging
3838895866534
Transport packaging weight
8.94 kg
Transport packaging volume
17.4
Pallet quantity
1404
Pallet volume
469.8
Classification
EC000003
Class name
Residual current circuit breaker (RCCB)
Additional equipment possible
No
Built-in depth
68mm
Degree of protection (IP)
IP20
Frequency
50/60 Hz
Leakage current type
A
Mounting method
DIN rail
Nominal rated current
63A
Nominal rated voltage
400/415V
Number of poles
4
Rated fault current
0,5mA
Selective protection
No
Short-circuit breaking capacity (Icw)
10kA
Short-time delayed tripping
No
Surge current capacity
0,4kA
Width in number of modular spacings
4
ETIM Classification – Version 7.0

Images & Diagrams

002061543RCCB, EFI-P4 A 63/0.5ASTIRCCBEFI-P4EFI-P4Type AInstantaneousModular current and residual protective devicesResidual current circuit breakers RCCB and accessoriesResidual current circuit breakers RCCBEFI-P4 A 63/0.5Function RCCBRated current 63AType ARated residual current 0,5ARated voltage 415VNo. Of poles 3+NRated AC voltage 400V 415VRated DC voltage 400V 415VCatalogue Group EFI-P4Rated Frequency 50Hz 60HzStandards IEC EN 61008Terminals 1-25Rated residual operating current IΔn 0.5ATripping time InstantaneousRated conditional short-circuit current Inc 10kARCCB EFI 63A 0.5A A 3+N 10kA Instantaneous